Water
Pressure For
the Estimating of Flow Rates and Water Usage
Water
pressure available has a significant influence on the gallon per
minute flow of the application. To illustrate this all important
factor, the chart below provides evidence that the water pressure
factor must be included in your sizing.
Variations
in Flows with a 50 Foot Garden Hose
Water
Pressure PSI
Flow GPM
10
7
20
9
30
11
40
13
50
15
70
18
100
22
Due
to the variation illustrated above, compensation must be applied
when calculating the flow demand on any application. Multiplication
factors must be applied upon completion of converting fixture value
to probable GPM flow. The chart in Figure A should be used for this
important adjustment. Example: A probable demand of 50 GPM was determined.
The application has an inlet pressure of 60 PSI. Using the chart
below, a multiple factor of 1.34 should be used. 50 GPM x 1.34 =
67 GPM compensated flow demand.
Figure
A
Pressure
PSI
Factor
20
0.74
30
0.92
35
1.00
40
1.07
50
1.22
60
1.34
70
1.46
80
1.57
90
1.68
100
1.78
*Charts
are based on inlet pressure of 35 PSI. For other pressures, adjust
by use of Figure A.
Figure
B
*Fixture Value Conversion Charts
Chart
I Country
Clubs, Hospitals, Hotels,
Nursing Homes,
Office Buildings, Shopping Centers, Schools, Restaurants
Chart
II Apartments,
Condominiums, Dormitories,
Trailer Parks,
Homes,
Motels
Fixture
Value
Probable
GPM Flow
Fixture
Value
Probable
GPM Flow
10
-
10
10
20
-
20
18
25
-
25
20
40
-
40
21
50
35
50
22
75
43
75
23
100
50
100
24
125
55
125
26
150
57
150
28
200
62
200
30
250
67
250
33
300
72
300
37
350
77
350
39
400
82
400
42
450
86
450
44
500
90
500
46
550
94
550
50
600
98
600
52
650
102
650
54
700
106
700
56
750
110
750
58
800
112
800
59
900
117
900
61
1,000
122
1,000
62
1,100
127
1,100
64
1,200
131
1,200
66
1,300
133
1,300
68
1,400
136
1,400
69
1,500
138
1,500
70
2,000
140
2,000
72
3,000
156
3,000
76
4,000
162
4,000
82
5,000
168
5,000
88
6,000
174
6,000
94
7,000
180
7,000
100
8,000
186
8,000
108
9,000
192
9,000
116
10,000
198
10,000
122
11,000
204
11,000
128
12,000
210
12,000
134
13,000
216
13,000
140
The
following is an example of estimating the probable GPM demand for
an apartment complex.
Customer: 160 unit apartment complex pressure at meter: 50 PSI